T6600 600V 200A AC/DC MULTI TESTER WITH FIELDSENSE TECHNOLOGY FLUKE T6
0

Your Cart is Empty

T6600 600V 200A AC/DC MULTI TESTER WITH FIELDSENSE TECHNOLOGY FLUKE T6-600

T6600 600V 200AMP AC/DC MULTI TESTER WITH FIELDSENSE TECHNOLOGY

Measure voltage without test leads

Measure voltage up to 600 V ac through the open fork, without test lead contact to live voltage.+ Without opening covers or removing wire nuts. On wires up to AWG 4/0 (120 mm2), carrying as much as 200 A. It will change your job. Safer. Faster. Easier.

Features

  • FieldSense technology for ac voltage, current and frequency measurement without making electrical contact to live voltage+
  • 1 to 600 V ac
  • 0.1 to 200 A ac
  • Resistance 1 ? to 2000 ?
  • Works with wires up to AWG 4/0 (120 mm2) with a 17.8 mm jaw opening
  • HOLD button temporarily freezes the reading for easy viewing
  • Easy to read display with backlight
  • Accepts optional Fluke TPAK Magnetic Meter Hanger for convenient operation
  • Standard two-year warranty; extendable to 4 years

{tab Specifications}

Measurement Specifications

Function

Requires
test leads

Range

Resolution

Accuracy[1]

FieldSense
ac voltage

No

600 V

1 V

±(3% + 3 counts) 45 Hz - 66 Hz[2][3]

FieldSense
ac current

No

200.0 A

0.1 A

±(3% + 3 counts) 45 Hz - 66 Hz

FieldSense
frequency (Hz)

No

1 Hz

±(1% + 2 counts)[3]

Volts ac

Yes

600 V

1 V

±(1.5% + 2 counts) 45 Hz - 66 Hz

Volts dc

Yes

600 V

1 V

±(1% + 2 counts)

Resistance

Yes

2000 ?

1 ?

±(1% + 2 counts)

Safety

600 V CAT III

Accuracy[1]: ± ( [ % of reading] + [number of least significant digits] ). Accuracy is specified for 1 year after calibration, at 18 °C to 28 °C (64 °F to 82 °F) with relative humidity to 90 %. AC measurements are ac-coupled, RMS responding.
Accuracy[2]: Add 3 % without an external ground connection. External ground connection required for user wearing insulated gloves, standing on an insulated ladder, or otherwise insulated from earth ground.
Accuracy[3]: FieldSense is specified from 16 V to 100 % of range.

General Specifications

Calibration

1-year calibration cycle

Dimensions

61.1 x 259.3 x 43.8 mm

Jaw opening

17.8 mm

Weight

0.35 kg (0.78 lb)

Temperature
Operating:
Storage:

-10 °C to +50 °C (14 °F to 122 °F)
-30 °C to +60 °C (-22 °F to +140 °F)

Altitude
Operating:
Storage:

2,000m (6,562 feet)
10,000 m (32,808 feet)

Relative Humidity

0% to 90%, 5 °C to 30 °C (41 °F to 86 °F)
0% to 75%, 30°C to 40 °C (86 °F to 104 °F)
0% to 45%, 40°C to 50 °C (104 °F to 122 °F)

Battery Type and Life

2 x AA (IEC LR6); 360 hours continuous, typical; 200 hours using FieldSense

Temperature coefficient

0.1 x (specified accuracy) / °C for <18°C or >28 °C
(< 64.4 °F or > 82.4 °F)

Safety

IEC/EN 61010-1: Pollution Degree 2

Electromagnetic Environment

IEC/EN 61326-1: Portable